Precautions for diesel generator design
- Categories:Industry News
- Author:
- Origin:
- Time of issue:2023-01-29 10:59
- Views:
(Summary description)Note 1: The oil storage room of the diesel generator room is not equipped with a breather pipe and a breather valve with a flame arrester. According to Clause 2 of Article 5.4.15 of Code for Fire Protection Design of Buildings GB500162014 (2018 Edition): "The oil tank in the oil storage room shall be sealed and equipped with a breather pipe leading to the outside. The breather pipe shall be equipped with a breather valve with a flame arrester (which must be indicated in the design description of electrical or HVAC drawings)." The correct approach is to set the site according to the requirements of the specification. The site selection should be concealed and not easily damaged. Note 2: Improper selection of detectors in diesel generator room and oil storage room. According to Article 5.4.13.6 of the Code for Fire Protection Design of Buildings GB500162014 (2018 Edition), "When automatic sprinkler systems are installed in other parts of the building, the diesel generator room shall be equipped with automatic sprinkler systems", the automatic sprinkler system fire extinguishing system is generally used in the generator room, and the thermal detector is selected for the generator room detector. The fire extinguishing form of the oil storage room is generally the dry powder automatic fire extinguishing system, because the control mode of the system is generally divided into two types (temperature control and electric control). If the electric control is required to be controlled by the fire alarm linkage, then the oil storage room detector should select the combination of temperature and smoke detectors, otherwise, the temperature detector can be selected. The correct way is to select the detectors in the generator room and oil storage room according to the fire extinguishing form of the room. Pay attention to confirm the fire extinguishing form of the above places with the water supply and drainage discipline. Note 3: The diesel generator room uses ordinary lamps; The common rocker switch for lighting in the oil storage room of diesel generator room is set in the oil storage room. According to the Code for Design of Electrical Installations in Explosive Atmospheres (GB500582014), the diesel oil with flash point greater than 60 ℃ is currently used in the self-provided diesel generator set, so the daily fuel tank room is classified as a non-explosive hazardous area. If the daily oil tank room is really designed according to the explosion hazard area, all disciplines such as architecture, structure, ventilation and electrical must consider explosion-proof, otherwise all previous efforts will be wasted; However, the current specifications or atlas examples obviously do not do this. The correct approach is to use sealed (waterproof and dustproof) ordinary lamps in the oil storage room of the diesel generator room. The lamp switch in the oil storage room can be installed outside the oil storage room and can be installed inside the oil storage room. The distribution box should not be installed in the oil storage room, and the junction box should also be sealed (waterproof and dustproof).
Precautions for diesel generator design
(Summary description)Note 1: The oil storage room of the diesel generator room is not equipped with a breather pipe and a breather valve with a flame arrester.
According to Clause 2 of Article 5.4.15 of Code for Fire Protection Design of Buildings GB500162014 (2018 Edition): "The oil tank in the oil storage room shall be sealed and equipped with a breather pipe leading to the outside. The breather pipe shall be equipped with a breather valve with a flame arrester (which must be indicated in the design description of electrical or HVAC drawings)."
The correct approach is to set the site according to the requirements of the specification. The site selection should be concealed and not easily damaged.
Note 2: Improper selection of detectors in diesel generator room and oil storage room.
According to Article 5.4.13.6 of the Code for Fire Protection Design of Buildings GB500162014 (2018 Edition), "When automatic sprinkler systems are installed in other parts of the building, the diesel generator room shall be equipped with automatic sprinkler systems", the automatic sprinkler system fire extinguishing system is generally used in the generator room, and the thermal detector is selected for the generator room detector.
The fire extinguishing form of the oil storage room is generally the dry powder automatic fire extinguishing system, because the control mode of the system is generally divided into two types (temperature control and electric control). If the electric control is required to be controlled by the fire alarm linkage, then the oil storage room detector should select the combination of temperature and smoke detectors, otherwise, the temperature detector can be selected.
The correct way is to select the detectors in the generator room and oil storage room according to the fire extinguishing form of the room. Pay attention to confirm the fire extinguishing form of the above places with the water supply and drainage discipline.
Note 3: The diesel generator room uses ordinary lamps; The common rocker switch for lighting in the oil storage room of diesel generator room is set in the oil storage room.
According to the Code for Design of Electrical Installations in Explosive Atmospheres (GB500582014), the diesel oil with flash point greater than 60 ℃ is currently used in the self-provided diesel generator set, so the daily fuel tank room is classified as a non-explosive hazardous area. If the daily oil tank room is really designed according to the explosion hazard area, all disciplines such as architecture, structure, ventilation and electrical must consider explosion-proof, otherwise all previous efforts will be wasted; However, the current specifications or atlas examples obviously do not do this.
The correct approach is to use sealed (waterproof and dustproof) ordinary lamps in the oil storage room of the diesel generator room. The lamp switch in the oil storage room can be installed outside the oil storage room and can be installed inside the oil storage room. The distribution box should not be installed in the oil storage room, and the junction box should also be sealed (waterproof and dustproof).
- Categories:Industry News
- Author:
- Origin:
- Time of issue:2023-01-29 10:59
- Views:
Note 1: The oil storage room of the diesel generator room is not equipped with a breather pipe and a breather valve with a flame arrester.
According to Clause 2 of Article 5.4.15 of Code for Fire Protection Design of Buildings GB500162014 (2018 Edition): "The oil tank in the oil storage room shall be sealed and equipped with a breather pipe leading to the outside. The breather pipe shall be equipped with a breather valve with a flame arrester (which must be indicated in the design description of electrical or HVAC drawings)."
The correct approach is to set the site according to the requirements of the specification. The site selection should be concealed and not easily damaged.
Note 2: Improper selection of detectors in diesel generator room and oil storage room.
According to Article 5.4.13.6 of the Code for Fire Protection Design of Buildings GB500162014 (2018 Edition), "When automatic sprinkler systems are installed in other parts of the building, the diesel generator room shall be equipped with automatic sprinkler systems", the automatic sprinkler system fire extinguishing system is generally used in the generator room, and the thermal detector is selected for the generator room detector.
The fire extinguishing form of the oil storage room is generally the dry powder automatic fire extinguishing system, because the control mode of the system is generally divided into two types (temperature control and electric control). If the electric control is required to be controlled by the fire alarm linkage, then the oil storage room detector should select the combination of temperature and smoke detectors, otherwise, the temperature detector can be selected.
The correct way is to select the detectors in the generator room and oil storage room according to the fire extinguishing form of the room. Pay attention to confirm the fire extinguishing form of the above places with the water supply and drainage discipline.
Note 3: The diesel generator room uses ordinary lamps; The common rocker switch for lighting in the oil storage room of diesel generator room is set in the oil storage room.
According to the Code for Design of Electrical Installations in Explosive Atmospheres (GB500582014), the diesel oil with flash point greater than 60 ℃ is currently used in the self-provided diesel generator set, so the daily fuel tank room is classified as a non-explosive hazardous area. If the daily oil tank room is really designed according to the explosion hazard area, all disciplines such as architecture, structure, ventilation and electrical must consider explosion-proof, otherwise all previous efforts will be wasted; However, the current specifications or atlas examples obviously do not do this.
The correct approach is to use sealed (waterproof and dustproof) ordinary lamps in the oil storage room of the diesel generator room. The lamp switch in the oil storage room can be installed outside the oil storage room and can be installed inside the oil storage room. The distribution box should not be installed in the oil storage room, and the junction box should also be sealed (waterproof and dustproof).